A modern, tightly built home depends on its ventilation system the way an older, drafty home never had to. An HRV or ERV quietly swaps stale indoor air for filtered outdoor air while holding on to most of the energy already in the house, and it runs in the background so reliably that most homeowners only notice it when it stops. The moment the grid goes down, the fans shut off, and a house designed around mechanical ventilation loses its dependable fresh-air supply, even though some air still seeps through gaps. An HRV battery backup solves that exact problem by keeping the fans—and in winter, the defrost and preheat system—running until the power returns.
This guide walks through how an HRV and an ERV actually use power, why the small fan wattage on the brochure tells only part of the story in cold weather, and how to size a battery so the ventilation keeps running for the full outage. The sizing math is straightforward once the hidden defrost load is brought into the open, and the calculator at the end does the arithmetic for your specific unit.
Quick Answer: Does an HRV/ERV Work During a Power Outage?
A standard HRV or ERV runs on 120-volt household power, and when that power is cut, the unit stops. The fans, the wall controller, and any electric defrost or preheat element all rely on grid electricity. The heat-exchange core itself is a passive block of metal or polymer, but without fans pushing air across it, it does nothing, so no fresh air moves through the house.
For a short outage, limited natural ventilation through a window can help when the outdoor air is safe and the weather allows. Wildfire smoke, outdoor pollution, or extreme cold can make opening windows a bad trade, so it is a conditional move rather than a default. To keep the mechanical ventilation going without windows, the unit needs either a battery or a generator supplying 120-volt power.
Three practical points frame the decision:
- A single-room or ductless unit is easy to back up. These draw only 8 to 50 watts, and a modest portable battery runs one for a day or more.
- A whole-home ducted system needs more careful sizing in winter. The fans are still modest, but an electric preheat element can pull 500 to 1,000 watts during defrost, and that peak has to be accounted for.
- Two separate questions decide the answer. The battery has to hold enough energy for the outage, and the inverter has to handle the highest instantaneous load. A battery that passes the first test can still trip on the second.
A whole-home battery ties this together cleanly and can cover the ventilation alongside other essentials. The home battery backup system overview explains how these units switch on automatically, and the how many kwh do i need guide translates appliance loads into a capacity figure.
In This Guide
- What HRVs and ERVs Do: Balanced Ventilation and Heat Recovery
- Why Ventilation Matters: Airtight Homes, CO2, Combustion Backdraft
- HRV vs ERV: Climate Choice and the Frost Difference
- Two Form Factors: Whole-Home Ducted vs Single-Room Ductless
- How Much Power an HRV/ERV Uses: Fan Watts by Speed
- From Fan Watts to Daily and Monthly kWh
- The Hidden Load: Defrost and Preheat Watts
- Recirculation vs Electric Preheat: Two Defrost Strategies
- Startup Surge: Why Fans Need Inverter Headroom
- Why a Small UPS Is Usually Not Enough
- Three Backup Paths: Portable, Critical-Load, Whole-Home
- HRV/ERV Battery Backup Sizing Table: 1, 3, 5, 7 Days
- Sizing the Inverter: Surge, Preheat, Pure Sine Wave
- Hardwiring, Critical-Load Subpanels and Outdoor Units
- Running an HRV on a Generator: Hybrid Backup
- Cold-Climate Install: Freeze Protection, Condensate, Location
- Worked Example: A 3-Day Winter Outage with Preheat
- HRV/ERV Battery Backup Calculator
- Bottom Line: Checks Before the Outage
What HRVs and ERVs Do: Balanced Ventilation and Heat Recovery
An HRV (heat recovery ventilator) and an ERV (energy recovery ventilator) are balanced ventilation systems, meaning they move two equal airstreams at the same time. One fan pulls fresh outdoor air in and distributes it through the supply ducts, while a second fan draws stale air from kitchens, bathrooms, and living spaces and exhausts it outdoors. The two streams pass through a heat-exchange core but never mix, so the outgoing air conditions the incoming air across the surface of the core.
In winter, the warm exhaust air preheats the cold incoming air, recovering a large share of energy that would otherwise be lost through an open window. Whole-home units commonly recover 60 to 80 percent of that heat. An ERV goes a step further and also transfers moisture, which helps in both dry winters and humid summers.
A few terms make the rest of the guide easier to follow:
- CFM (cubic feet per minute) is the standard measure of airflow, describing how much air a fan moves.
- Heat exchanger is the core where energy transfers between the two airstreams without them touching.
- EC motor is an electronically commutated, high-efficiency fan motor that uses less power at low speeds.
- Makeup air is the replacement outdoor air brought in to balance air exhausted from the house.
- Supply and exhaust air are the two streams: fresh air supplied indoors and stale air exhausted out.
It is worth being clear that heat recovery lowers the heating and cooling load; it does not generate electricity. The fans still need power, which is why an HRV battery backup matters. The solar battery sizing guide covers the broader method of matching loads to storage.
Why Ventilation Matters: Airtight Homes, CO2, Combustion Backdraft
New homes are built tight for good reason. Air sealing is one of the cheapest ways to cut energy use, but a tight envelope also shuts off the natural infiltration that used to refresh indoor air on its own. When a balanced ventilator is the main source of fresh air, shutting it off means pollutants, moisture, and carbon dioxide start building up indoors. Carbon dioxide rises steadily as people breathe, and over hours a closed room can feel stuffy and dull.
The second concern involves combustion appliances. Furnaces, water heaters, fireplaces, and gas ranges need their own combustion air and a clear vent path. If a house runs negative pressure because exhaust fans are running without balanced intake, a draft hood can backdraft and pull combustion gases, including carbon monoxide, back into living space. A balanced HRV or ERV limits the pressure imbalance its own ventilation creates, which helps appliances vent as designed. It does not replace the dedicated combustion air or sealed-combust design an appliance requires, and backing it up is not a safeguard against carbon monoxide backdraft. Naturally drafting appliances should be tested for combustion safety and negative pressure by a qualified person.
The EPA guidance on protecting indoor air quality points to using and maintaining the ventilation system as a core step, and the can a solar battery run a heat pump article looks at how all-electric homes manage these loads. The value of keeping ventilation powered during an outage fits the same electrification picture, while ventilation design and appliance venting follow mechanical codes and manufacturer specs, so the practical sizing here focuses on the electrical side.
HRV vs ERV: Climate Choice and the Frost Difference
The choice between the two starts with what each core transfers. An HRV transfers only sensible heat, so it suits cold, dry climates and homes where indoor moisture runs high and needs to be removed. An ERV transfers both heat and moisture, making it the common pick in humid and mixed climates where it keeps summer humidity from flooding in and holds some moisture indoors in winter.
An ERV is not a dehumidifier. It moves moisture across the core to balance conditions, but where humidity is genuinely a problem, a separate dehumidifier still does the real work. The Building Science Corporation guidance on balanced ventilation lays out these climate and humidity rules clearly, including the limits of each core type.
| Factor | HRV | ERV |
|---|---|---|
| Transfers | Sensible heat only | Heat and moisture |
| Best climate | Cold, dry; high indoor moisture | Humid and mixed |
| Liquid condensate | Yes, needs drain | Often little or none |
| Frost resistance | Lower, often needs defrost | Up to about 18°F lower in some manufacturer data |
| Typical preheat load | Common in cold climates | Often none, but model-dependent |
For backup power, frost behavior is the key. In a static-plate ERV, moisture crosses the enthalpy core as water vapor rather than condensing into liquid, so there may be no drain pan full of water to freeze. Manufacturer data for one residential line shows an ERV tolerating an outdoor temperature roughly 18°F lower than a comparable HRV, but that gap is a product-specific design result, not a universal rule, and some ERVs still offer timed exhaust or electric preheat as options. The frost-control temperature, defrost method, and any extra load for a given unit come from its installation manual. Where an ERV genuinely avoids defrost, the winter backup load shrinks because there is no electric preheat element to power.
Two Form Factors: Whole-Home Ducted vs Single-Room Ductless
HRVs and ERVs come in two distinct shapes, and the form factor drives both the power draw and the backup plan.
A whole-home ducted unit is a central box connected to supply and exhaust ducts that serve every room. It moves the most air, runs two fans, and typically draws 50 to 200 watts depending on speed. It is the standard choice in new construction where ductwork is designed in from the start. A single-room or ductless unit mounts through an exterior wall with one hole and no ducts, serving a single space. Decentralized systems use several of these small units, each working independently, and they draw only 8 to 50 watts.
Here is how the two forms compare.
| Feature | Whole-home ducted | Single-room ductless |
|---|---|---|
| Installation | Central box with ductwork | One wall hole, no ducts |
| Coverage | Entire house | One room, or several independent units |
| Typical fan power | 50–200 W | 8–50 W |
| Defrost/preheat | Often includes electric preheat | Usually none |
| Backup difficulty | Moderate, winter peak matters | Easy, small battery suffices |
Because the single-room form is so light, it backs up with a compact battery, while the whole-home form needs the defrost-aware sizing covered later.
How Much Power an HRV/ERV Uses: Fan Watts by Speed
The fan wattage depends on the form factor and the speed setting. Whole-home units running at normal speed land in the 50-to-200-watt range, with low speed around 30 to 80 watts and a boost setting around 80 to 200 watts. Single-room and decentralized units run far lower, typically 8 to 50 watts, with some of the smallest decentralized fans using 8 to 35 watts.
These are running watts, describing the fan while it is actually turning. A fan can draw a startup surge around two to three times its running figure for a split second, but that is only a rough guide; EC motors and electronic controllers behave differently, so the manual's startup current or maximum input is the figure to trust. The table below groups the fan loads by form and speed.
| Form and speed | Typical running watts |
|---|---|
| Whole-home, low | 30–80 W |
| Whole-home, normal | 50–150 W |
| Whole-home, boost | 80–200 W |
| Single-room, normal | 8–35 W |
| Single-room, high | 30–50 W |
Exact figures come from the unit's nameplate or manual, and reading them directly is the reliable starting point for sizing. The what size inverter for a 48v battery guide explains how running watts and surge watts map to inverter ratings.
From Fan Watts to Daily and Monthly kWh
Turning fan watts into energy is a simple conversion. Daily energy in kilowatt-hours equals the wattage multiplied by the hours the fan runs each day, divided by 1,000.
A useful benchmark is a 100-watt fan running continuously. That uses 100 × 24 ÷ 1,000 = 2.4 kWh a day, or about 72 kWh over a month. Across a year, the fan energy for whole-home systems typically lands in the 350-to-575 kWh range. Most systems do not run at full tilt around the clock; timers, humidity sensors, and CO2 controllers cycle the speed, so real consumption usually sits below the continuous figure.
The lookup table below shows daily and monthly energy for common fan wattages, assuming continuous running.
| Fan watts | Daily kWh | Monthly kWh |
|---|---|---|
| 30 W | 0.72 | 21.6 |
| 60 W | 1.44 | 43.2 |
| 100 W | 2.40 | 72.0 |
| 150 W | 3.60 | 108.0 |
| 200 W | 4.80 | 144.0 |
Battery capacity is rated in the same kWh units, and the usable portion depends on depth of discharge. The lifepo4 depth of discharge article explains why a lithium battery can use far more of its rated capacity than a lead-acid one.
The Hidden Load: Defrost and Preheat Watts
The fan wattage is the number printed on the brochure, but in cold weather it is not the whole load. HRVs pulling frigid outdoor air can freeze condensation inside the core, so units built for cold climates include a defrost system. The ones that use electric resistance heat to preheat incoming air can draw 500 to 1,000 watts while the element is on, far above the fan's running figure.
The preheat does not run on a fixed schedule. Temperature sensors switch it on as the unit approaches freezing, commonly around 23°F (-5°C) in some models, and the timing varies by controller and outdoor conditions. The CCHRC overview of heat recovery ventilation describes different units taking different approaches: some recirculate indoor air, while a cold-climate model uses a 1,000-watt electric resistance heater or a ground loop. For a consistent planning number, the worked example below assumes five minutes of preheat per hour; that is an explicit assumption, not an industry-standard cycle, and a real project should use the specific model's preheat watts and control logic.
Sizing the inverter and battery only from the fan watts understates the real demand. The preheat element, even running a fraction of the hour, adds both daily energy and a high instantaneous peak. Battery behavior in these temperatures also matters, which the temperature impact on lithium ion battery lifespan article explores in detail.
Recirculation vs Electric Preheat: Two Defrost Strategies
Cold-climate HRVs use two distinct strategies to keep the core from freezing, and the choice changes both the energy use and the ventilation delivered.
The first is recirculation, sometimes called damper defrost. The unit redirects warm indoor air back through the core to thaw it, using no electric heater. It adds almost no electrical load, but during the recirculation period it stops bringing in fresh outdoor air, so the effective ventilation rate drops. The second is electric preheat, which warms the incoming air before it reaches the core so ventilation continues uninterrupted. It pulls that high 500-to-1,000-watt load, but it keeps fresh air moving, and cold-climate research finds that per unit of fresh air delivered, preheat can be more efficient than repeatedly sacrificing ventilation to recirculation.
The table below compares the two.
| Factor | Recirculation | Electric preheat |
|---|---|---|
| Extra electrical load | Almost none | 500–1,000 W peak |
| Fresh air during defrost | Paused | Continues |
| Daily energy | Lower | Higher |
| Best fit | Moderate cold, lower budget | Very cold, continuous ventilation needed |
The defrost strategy is an explicit input in the calculator, because it changes the result substantially. The inverter shuts down with battery left guide explains what happens when an inverter meets a load it cannot handle, which is exactly the failure to avoid when preheat is involved.
Startup Surge: Why Fans Need Inverter Headroom
Fan motors can draw a startup surge for the instant they spin up, and a whole-home unit with two fans can occasionally see both start together across a long outage. The inverter has to cover that worst-case moment rather than the average, using the manual's startup current where available rather than a generic multiplier.
In a unit with electric preheat, the heating element is usually the highest instantaneous load of all. A 1,000-watt element outranks the fan surge, so it sets the peak the inverter must handle, and it runs for minutes rather than the split-second window of a motor surge. This is the second half of the sizing rule: enough stored energy covers the days, but enough instantaneous power covers the peak, and the two are independent. A battery can hold days of energy and still trip the moment the preheat or a fan surge lands.
The modular battery vs single unit battery storage comparison covers how multiple units and inverters distribute these loads.
Why a Small UPS Is Usually Not Enough
A plug-in office UPS is built to carry a computer or router for a few minutes so work can be saved and the machine shut down gracefully. Most use small sealed lead-acid batteries, and they are not designed to run fans for days or to absorb a preheat peak. Plugging a whole-home HRV into one generally trips the UPS the moment the fans or heater draw their surge.
A UPS can make sense for the smallest single-room units during very short outages, where the load is only a few dozen watts. Beyond that, a genuine HRV battery backup with a proper inverter and enough capacity is the sound choice. The honest flip side is that overbuying is a real waste too. If outages are rare and the only load is a small ductless fan, a compact portable unit is the right answer rather than a large whole-home battery.
The home energy storage vs outdoor portable power guide draws the line between installed storage and portable gear.
Three Backup Paths: Portable, Critical-Load, Whole-Home
There are three ways to back up an HRV or ERV, and the right one follows the home and the outage.
A portable power station is the simplest. The ventilation unit plugs into it during an outage, with no wiring or permits, and it suits renters, short outages, and single-room units. It is mostly a 120-volt solution, so its continuous and surge ratings set the ceiling. A critical-load subpanel is the middle path: the HRV circuit moves onto a backup subpanel that a battery powers, allowing a hardwired connection with moderate capacity. A whole-home battery is the most capable, tying into the main panel to cover multiple circuits, run for days, and recharge from solar or a generator.
The table below compares the three.
| Factor | Portable station | Critical-load subpanel | Whole-home battery |
|---|---|---|---|
| Installation | None, plug in | Subpanel and wiring | Main panel integration |
| Connection | Corded | Hardwired | Hardwired |
| Typical voltage | 120V | 120V | 120/240V |
| Best for | Renters, short outages | Targeted hardwired backup | Multi-day, multiple loads |
| Handles preheat | If rated for the peak | Yes, with proper inverter | Yes |
A battery can also be charged purely from the grid with no solar panels, which the install a home battery without solar guide explains.
HRV/ERV Battery Backup Sizing Table: 1, 3, 5, 7 Days
The sizing table matches battery capacities against outage length. The AC energy each battery can deliver is the rated capacity multiplied by a planning efficiency of 0.81, covering inverter and battery losses. That gives usable AC figures of 4.05 kWh for a 5 kWh unit, 12.96 for 16 kWh, 16.20 for 20 kWh, 24.30 for 30 kWh, and 32.40 for 40 kWh.
The whole-home profile with preheat runs about 4.4 kWh a day, which sets the AC need at 4.4 for one day, 13.2 for three days, 22.0 for five days, and 30.8 for seven days. Each cell is marked Enough or Short against that need.
| Battery | AC delivered | 1 day | 3 days | 5 days | 7 days |
|---|---|---|---|---|---|
| 5 kWh | 4.05 kWh | Short | Short | Short | Short |
| 16 kWh | 12.96 kWh | Enough | Short | Short | Short |
| 20 kWh | 16.20 kWh | Enough | Enough | Short | Short |
| 30 kWh | 24.30 kWh | Enough | Enough | Enough | Short |
| 40 kWh | 32.40 kWh | Enough | Enough | Enough | Enough* |
\*At seven days the 40 kWh unit holds only about 1.6 kWh of headroom, before extra loads, cold weather, aging, or a design reserve. Enough means the theoretical energy is met; Short means it is not.
The single-room profile sits around 0.72 kWh a day. A 5 kWh battery (4.05 kWh delivered) covers it for about five days, while a 16 kWh unit covers the full week with margin. Swapping in the real nameplate figures is the way to refine any of these numbers.
The 0.81 figure is a planning assumption, not a product spec. The 16 kWh JM battery is rated for 80% depth of discharge, so using that DoD with a 90% inverter gives about 16 × 0.80 × 0.90 = 11.52 kWh of usable AC, lower than the 12.96 in the generic table. A real product decision should use the model's own DoD and the inverter efficiency, and the BMS limits must be checked alongside the capacity. The home battery sizing 15 vs 20 vs 30 kwh guide walks through the tier choices, with runtime detail in how long will 20kwh power a house and how long will a 40kwh battery last.
The matching JM products cover the full range. The 5kWh Wall-Mounted LiFePO4 Battery fits the single-room profile, while the 16kWh Solar Battery and 20kWh Moveable LiFePO4 Battery cover whole-home multi-day use, with the 30kWh Moveable Lithium Solar Battery and 40kWh LiFePO4 Battery for the longest outages.
Sizing the Inverter: Surge, Preheat, Pure Sine Wave
The inverter has to clear two bars. Its continuous rating needs to cover the loads that run at the same time—the fans, the controller, and the preheat element while it is on—with headroom. Because preheat runs for minutes, not the split-second surge window, a 400-watt continuous inverter cannot carry a 1,000-watt heater even if its peak rating looks high. The peak or surge rating separately handles the motor startup.
A pure sine wave inverter is the right choice. Modified sine wave power can run rough on fan motors, raising heat and noise, and it can interfere with the electronic control boards that manage the unit. Pure sine wave output matches grid power and protects those controls. The BMS discharge current, the 120/240-volt requirement, and the fan nameplate all need to line up.
Here are the minimum inverter figures for the whole-home scenario with a 1,000-watt preheat.
| Requirement | Minimum for whole-home with preheat |
|---|---|
| Continuous output | Cover the 1,000 W preheat plus fans; recommend a 1,200–1,500 W class |
| Peak/surge | Per the manual's startup current; recommend 1,500–2,000 W with a stated duration |
| Waveform | Pure sine wave |
| BMS current at a 2,000 W peak | About 46 A on a 48 V system (about 23 A at 1,000 W) |
The BMS has to be checked against the inverter peak, not just the preheat, accounting for the lower battery voltage near empty and the BMS continuous and peak discharge limits. The what size solar battery do you need for a power outage guide ties these inverter and capacity checks together.
Hardwiring, Critical-Load Subpanels and Outdoor Units
The three connection methods each have their place. Plugging into a portable station needs no wiring and stays flexible. Moving the HRV circuit onto a critical-load subpanel gives a hardwired backup that switches on automatically. An automatic transfer switch can manage the changeover between grid and battery without interruption.
Where the unit or battery sits outdoors or in an unheated garage, freeze protection, grounding, and the dedicated circuit all matter. Anti-backfeed protection, proper grounding, double-pole breakers, and dedicated circuits are installed to local electrical codes by a licensed electrician. The solar battery installation location guide covers placement, and 7 common mistakes when installing home energy storage flags the typical wiring and sizing errors.
Running an HRV on a Generator: Hybrid Backup
A generator can run an HRV directly, but the cleaner setup is a hybrid. The battery carries the quiet day-to-day ventilation and short outages, and a generator steps in during a long, cold outage to recharge the battery or share the preheat load. That keeps the fans running on silent battery power most of the time while the generator works only when needed.
Battery and generator differ on the same five dimensions: noise, exhaust, maintenance, runtime, and automatic switching. A battery is silent, has no fumes, and needs almost no maintenance, while a generator runs as long as fuel lasts but carries noise and carbon monoxide risk and needs regular servicing. A fuel-burning generator stays outdoors, away from doors, windows, vents, and the HRV outdoor intake, so its exhaust is not pulled back into the supply airstream. The home energy storage vs standby generators comparison lays these out, and hybrid solar inverter on a generator addresses running the two together safely.
Cold-Climate Install: Freeze Protection, Condensate, Location
In ice-storm country, the cold-climate details decide whether a unit survives an outage cleanly. HRVs can produce liquid condensate during defrost, and that water needs a drain path that will not freeze. After a shutdown, natural chimney effect can pull cold outdoor air through the ducts and freeze the core, so the manufacturer's shutdown and freeze-protection instructions for the exact model are the steps to follow; not every unit has a manual outdoor damper, and not every drain line is meant to be drained by the homeowner.
Some ERV designs reduce this problem. The CCHRC cold-climate research measured an HRV core producing many liters of condensate over a week while an ERV core produced no measurable amount, but that result is design-specific, and some HRV/ERV units can still produce occasional condensate, so the manual still governs whether a drain is required.
Battery charging in the cold follows its own rules, covered in lifepo4 winter charging guide and winter home solar battery guide.
Worked Example: A 3-Day Winter Outage with Preheat
A concrete example ties the method together. The setup is a whole-home HRV with a 100-watt fan running continuously, a 1,000-watt preheat element assumed to run five minutes each hour, no other loads, a three-day outage, and 0.81 planning efficiency.
First, the fan energy: 100 W × 24 hours ÷ 1,000 = 2.4 kWh a day. The assumed preheat runs five minutes an hour, which is two total hours a day at 1,000 watts, adding 2.0 kWh. Combined daily AC load is 4.4 kWh. Converting to the nominal battery requirement, 4.4 ÷ 0.81 = 5.43 kWh a day. Over three days, that is 13.2 kWh of AC energy, or about 16.3 kWh of nominal battery capacity.
Against the capacity tiers, the 5 and 16 kWh batteries fall short, because the 16 kWh unit delivers only 12.96 kWh against a 13.2 kWh need; the 20 kWh battery is the first tier that passes. The highest instantaneous load is the 1,000-watt preheat, which sets the inverter peak, and the BMS current at that load on a 48-volt system is about 23 amps, rising to roughly 46 amps if the inverter reaches a 2,000-watt peak. The inverter recommendation is a 1,200-to-1,500-watt continuous class with a 1,500-to-2,000-watt peak and pure sine output.
For contrast, a single-room ductless unit at 30 watts uses only 0.72 kWh a day, and a small portable battery covers it through the same three-day outage with ease. If even the largest battery is stretched, the honest moves are shedding nonessential loads, recharging from solar or a generator, or expanding capacity rather than pretending one unit can do everything. Runtime framing for the mid-tier option is in how long will a 15kwh battery power a house.
HRV/ERV Battery Backup Calculator
The calculator below turns the manual method into instant results for sizing an HRV or ERV battery backup. Enter the unit's real nameplate figures, choose the form factor and defrost strategy, and it returns the capacity and inverter answers in two separate blocks.
The inputs cover the variables that actually change the result:
- Form factor selects whole-home ducted versus single-room ductless.
- Type selects HRV versus ERV, which adjusts the defrost assumption.
- Fan running watts and daily run hours set the base fan energy.
- Fan startup surge captures the motor's momentary peak.
- Defrost strategy chooses none, recirculation, or electric preheat.
- Preheat watts and defrost minutes per hour model the hidden winter load.
- Other loads, outage days, and system efficiency complete the picture.
The capacity block reports daily fan, preheat, and combined kWh, the nominal daily requirement, the multi-day total, and an Enough or Short verdict for each capacity tier, along with runtime days. The compatibility block reports the highest instantaneous watts, the recommended continuous and peak inverter ratings, the BMS current, and the pure sine wave reminder. Choosing an ERV automatically reduces or removes the defrost load, and recirculation lowers energy while pausing fresh air.
The tool is an estimate for planning, and the hardwired connection itself is installed by a licensed electrician to local codes.
Size your HRV/ERV battery backup
Choose the form, type, and defrost strategy, then confirm the nameplate figures. Energy (capacity) and equipment compatibility (inverter and BMS) are reported as two separate results.
Results will appear here after you press the button.
Frequently Asked Questions
Does an HRV/ERV work during a power outage?
A standard unit runs on 120-volt power and stops the moment that power is cut. The fans and controller rely on electricity, and the passive core cannot move air without them. Limited natural ventilation through a window can help when the outdoor air is safe, while a battery or generator keeps the mechanical ventilation running.
How much power does an HRV use?
Whole-home units draw 50 to 200 watts depending on speed, while single-room ductless units draw only 8 to 50 watts. A 100-watt fan running continuously uses about 2.4 kWh a day. The exact figure is on the unit's nameplate.
Do I still need defrost backup if I install an ERV?
A static-plate ERV moves moisture as vapor and often produces little or no liquid condensate, so it can resist frost and may need no defrost. Some manufacturer data shows an ERV tolerating an outdoor temperature about 18°F lower than a comparable HRV, but the exact frost temperature and any defrost option depend on the model and its manual.
What size battery do I need for an HRV?
Start with the fan daily kWh, then add the preheat energy if the unit uses electric defrost. A whole-home unit with preheat at 4.4 kWh a day needs about 20 kWh of nominal capacity for a three-day outage, since the 16 kWh tier falls just short, while a single-room unit backs up with a much smaller battery.
Can a portable power station run an HRV in winter?
It can if its continuous and peak ratings cover both the fans and the preheat element. The 500-to-1,000-watt preheat is the limiting factor, so checking the station's surge rating matters more than its fan-only math. A small station handles a ductless unit easily.
Will a modified sine wave inverter harm HRV controls?
Pure sine wave is recommended. Modified sine power can make fan motors run hotter and louder and can interfere with the electronic control boards. Pure sine output matches grid power and protects the unit.
Can I run my HRV on a generator?
Yes, and a hybrid arrangement works best, with the battery carrying quiet everyday ventilation and the generator recharging it or sharing the preheat load during a long outage. The generator runs as long as fuel lasts but adds noise and maintenance.
Will an HRV bring in cold air or freeze in winter?
Cold-climate units handle this with either recirculation or electric preheat to keep the core from freezing. Recirculation pauses fresh air during defrost, while preheat keeps ventilation going at the cost of a high electrical peak. Following the manufacturer's cold-weather procedure protects the core.
Bottom Line: Checks Before the Outage
Backing up an HRV or ERV comes down to a short list of concrete checks. Read the fan running watts and any preheat rating off the nameplate, decide whether the unit is whole-home or single-room, and confirm which defrost strategy it uses. Convert those figures to daily kWh, multiply by the outage length, and divide by system efficiency to get the nominal battery size. Then check the inverter peak against the preheat or fan surge, confirm pure sine output, and have the hardwired connection installed to local code.
For a single-room ductless unit, a compact ERV battery backup finishes the job. For a whole-home ducted system in a cold climate, a 20 kWh-class battery with a 1,200-to-1,500-watt continuous inverter carries three days of ventilation, and larger units or a hybrid generator extend that further. Getting these two independent answers right—enough energy and enough instantaneous power—is what keeps the fresh air moving until the grid comes back.